Metasys N2 Communications

u

Drive Functions

Each of the following functions must be enabled during start-up of the drive:

n

Start and Stop the Drive

Set the Run Forward Command (BO 1) to run the drive in the forward direction. Set the Run

Reverse Command (BO 2) to run the drive in the reverse direction. Run/Stop Monitor (BI 1)

shows the current run status of the drive. Forward/Reverse Monitor (BI 2) shows the current

direction.

NOTICE: Damage to Equipment. Improper drive direction may damage HVAC equipment if parameter b1-04,

Reverse Enable, is set to 0 (Enable). Confirm proper motor rotation prior to connecting the load to the motor.

n

Lock the Drive Panel

Locking the panel prevents the user from using the LOCAL/REMOTE and STOP keys locally

at the drive panel. Panel Lock (BO 10) can be commanded to lock and unlock the panel.

n

Digital Inputs

Multi-Function Input S3 (BO 5) through Multi-Function Input S7 (BO 9) are physical digital

inputs on the drive. They can be set either by external devices, such as limit or pressure

switches, or by the network. Their function depends on how the drive has been programmed.

Refer to the drive manual section on Multi-Function Inputs (H1-03 through H1-07) for detailed

information on the use and programming of the multi-function inputs. The multi-function

input status can be monitored through Multi-Function Input 1 Monitor (BI 14) through Multi-

Function Input 5 Monitor (BI 19).The multi-function inputs can be set by both external devices

or over the network.

Note:

The multi-function inputs can be set by both external devices or over the network. Use caution when

connecting the multi-function inputs to external devices to ensure correct system operation.

n

Loop Gain

PI Proportional Gain (AO 4) and PI Integral Time (AO 5) are the gain and integral time

parameters used by the drive. The PI loop is structured differently than the Metasys loop.

Refer to the drive manual section on PID for information on how the PI loop functions.