10 apogee fln p1 communications – Yaskawa APOGEE FLN P1 User Manual
Page 40

Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Parameter
25
LDI
ZERO SPEED
OFF
-
1
0
ON
OFF
U1-12
(Bit 1)
26
LDI
SPEED AGREE
NO AGR
-
1
0
AGREE
NO AGR
U1-12
(Bit 4)
27
LDI
DRIVE READY
NOTRDY
-
1
0
READY
NOTRDY
U1-12
(Bit 5)
28
LDI
LOC.REM MON
REMOTE
-
1
0
LOCAL
REMOTE
-
29
LDO
DAY.NGT
DAY
-
1
0
NGT
DAY
-
30
LAO
CURRENT LMT
0
A
0.01
0
-
-
E2-01
31
LAO
ACCEL TIME
0
s
0.1
0
-
-
C1-01
32
LAO
DECEL TIME
0
s
0.1
0
-
-
C1-02
33
LDO
LOCK PANEL
UNLOCK
-
1
0
LOCK
UNLOCK
-
35
<1>
LDO
RUN ENABLE
STOP
-
1
0
ENABLE
STOP
-
36
LAO
STALL PRE RN
90
%
1
30
-
-
L3-06
37
LAO
STALL PRE AC
120
%
1
0
-
-
L3-02
38
LAO
FREQ UP LIM
100
%
0.1
0
-
-
d2-01
39
LAO
FREQ LOW LIM
0
%
0.1
0
-
-
d2-02
40
LDI
MULTI OUT 1
OFF
-
1
0
ON
OFF
U1-11
(Bit 0)
41
LDI
MULTI OUT 2
OFF
-
1
0
ON
OFF
U1-11
(Bit 1)
42
LDI
MULTI OUT 3
OFF
-
1
0
ON
OFF
U1-11
(Bit 2)
43
LDI
SAFETY ILOCK
OFF
-
1
0
ON
OFF
U1-10
(Bit 2)
44
LDO
MF INP 1
OFF
-
1
0
ON
OFF
-
45
LDO
MF INP 2
OFF
-
1
0
ON
OFF
-
46
LDO
MF INP 3
OFF
-
1
0
ON
OFF
-
47
LDO
MF INP 4
OFF
-
1
0
ON
OFF
-
48
LDO
MF INP 5
OFF
-
1
0
ON
OFF
-
49
LAO
JUMP FREQ 1
0
Hz
0.1
0
-
-
d3-01
50
LAO
JUMP FREQ 2
0
Hz
0.1
0
-
-
d3-02
51
LAO
JUMP FREQ 3
0
Hz
0.1
0
-
-
d3-03
52
LAO
JUMP FREQ BW
0
Hz
0.1
0
-
-
d3-04
53
LAO
NUM AUTOSTRT
0
-
1
0
-
-
L5-01
10 APOGEE FLN P1 Communications
40