Object
ID
Object Name
Units
Default Value
Yaskawa Drive
Parameter
AO 13
Motor Rated Current
A
Motor model dependent
E2-01
AO 14
Jump Frequency 1
0.1 Hz
0.0
d3-01
AO 15
Jump Frequency 2
0.1 Hz
0.0
d3-02
AO 16
Jump Frequency 3
0.1 Hz
0.0
d3-03
AO 17
Jump Frequency Bandwidth
0.1 Hz
1.0
d3-04
AO 18
Number of Auto Restarts
-
0
L5-01
AO 19
Operator Display Mode
-
0
o1-03
AO 20
Power Loss Ride-Thru
seconds
Drive model dependent
L2-02
AO 21
Cable Loss Timeout
seconds
2.0
F6-77
AO 22
Cable Loss Speed
0.01 Hz
0.00
d1-04
AO 23
PI Integral Limit
0.1%
100.0
b5-04
AO 24
PI Upper Limit Value
0.1
100.0
b5-06
AO 25
PI Offset Adjustment
0.1
0.0
b5-07
AO 26
PI Primary Delay Time
0.01
0.00
b5-08
AO 27
PI Feedback Reference Missing
Detection Select
1
0
b5-12
AO 28
PI Feedback Reference Missing
Detection Level
1%
0
b5-13
AO 29
PI Feedback Reference Missing
Detection Time
0.1 s
1.0
b5-14
AO 30
Read Parameter Number
-
-
-
AO 31
Write Parameter Number
-
-
-
AO 32
Write Parameter Data
-
-
-
n
Metasys N2 Binary Input (BI) Summary
Table 12 Metasys N2 Binary Input Summary (SI-J3 to Metasys N2)
Object
ID
Object Name
Default
Off (0) State
On (1) State
BI 1
Run/Stop Monitor
0
Stopped
Running
BI 2
Forward/Reverse Monitor
0
Forward
Reverse
BI 3
Drive Ready Monitor
0
Not Ready
Ready
BI 4
Fault Monitor
0
Not Faulted
Faulted
BI 5
Zero Speed
0
Not Zero Speed
Zero Speed
BI 6
Speed Agree
0
Not Speed Agree
Speed Agree
BI 7
Minor Fault
0
No Minor Fault
Minor Fault
BI 8
Major Fault
0
No Major Fault
Major Fault
BI 9
Drive Communication Error
Monitor
0
No Error
Error
9 Metasys N2 Communications
YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual