beautypg.com

Option led display, 4 option components – Yaskawa APOGEE FLN P1 User Manual

Page 11

background image

u

Option LED Display

The option has four LEDs.
Two bi-color Status LEDs:
• Module status (MS) red/green
• Network status (NS) red/green
Two Network LEDs:
• Transmit (TX) green
• Receive (RX) green
The operational states of the option LEDs after completion of the power-up diagnostic LED

sequence are described in

Table 3

. Wait at least 2 seconds for the power-up diagnostic process

to complete before verifying LED states.

Table 3 Option LED States

Name

Display

Operating Status

Remarks

Color

Status

MS

-

OFF

Power supply OFF

Power is not being supplied to the drive.

Green

ON

Normal operation

The option is operating normally and

initialization is complete.

Green

Flashing

Standby/Initializing

The option is in process of configuring or

waiting for configuration information.

Red

Flashing

Minor fault

The option has detected a recoverable minor

fault such as incomplete configuration.

Red

ON

Major fault

The option has detected an unrecoverable

major fault.

Green/Red

Flashing

Option self-test

The option is in self-test mode.

NS

-

OFF

Power supply OFF

-

Green

ON

Connected

The device is currently communicating on the

network.

Green

Flashing

Not connected

The device currently is not communicating, but

is correctly configured. The state is waiting for

communication to resume.

Red

Flashing

Minor fault

A minor recoverable fault has occurred.

Red

ON

Major fault

A non-recoverable major network fault has

occurred.

Green/Red

Flashing

Network test

Power-up sequence and testing

TX

-

OFF

No data being sent to the

network

This node is not sending any data.

Green

Flashing

Data being sent to the

network

This node is sending network data.

4 Option Components

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual

11