Page 32

Object
ID
Object Name
Default
Off (0) State
On (1) State
BI 10
Multi-Function Output 1
(H2-01)
0
Off
On
BI 11
Multi-Function Output 2
(H2-02)
0
Off
On
BI 12
Multi-Function Output 3
(H2-03)
0
Off
On
BI 13
Safety Interlock Monitor
0
Safety Clear Terminal 3 Closed
Safety Set Terminal 3 Open
BI 14
HAND/AUTO Reference
Monitor
0
REMOTE
LOCAL
BI 14
Multi-Function Input S3
Monitor
0
Off
On
BI 16
Multi-Function Input S4
Monitor
0
Off
On
BI 17
Multi-Function Input S5
Monitor
0
Off
On
BI 18
Multi-Function Input S6
Monitor
0
Off
On
BI 19
Multi-Function Input S7
Monitor
0
Off
On
n
Metasys N2 Binary Output (BO) Summary
Table 13 Metasys N2 Binary Output Summary (Metasys N2 to SI-J3)
Object ID
Object Name
Default
Off (0) State
On (1) State
BO 1
Run Forward Command
0
Stop
Forward
BO 2
Run Reverse Command
0
Stop
Reverse
BO 3
Serial Fault (EF0) Command
0
No Fault
Fault
BO 4
Fault Reset Command
0
No Reset
Reset
BO 5
Multi-Function Input S3 (H1-03)
0
Off
On
BO 6
Multi-Function Input S4 (H1-04)
0
Off
On
BO 7
Multi-Function Input S5 (H1-05)
0
Off
On
BO 8
Multi-Function Input S6 (H1-06)
0
Off
On
BO 8
Multi-Function Input S7 (H1-07)
0
Off
On
BO 10
Panel Lock
0
LOCAL/REMOTE and Stop/
Reset Keys Enabled
LOCAL/REMOTE and
Stop/Reset Keys Disabled
BO 11
Communication Fault Enable
0
BUS Fault Not Activated if
Cable Loss Occurs
BUS Fault Activated if
Cable Loss Occurs
u
Metasys N2 Cable Loss Configuration and Behavior
This section describes the configurable cable loss feature of the drive. This feature offers a
user maximum flexibility in determining drive response to a loss of communication.
9 Metasys N2 Communications
32
YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual