10 apogee fln p1 communications – Yaskawa APOGEE FLN P1 User Manual
Page 39

Information to consider when referencing this table:
1.
Points not listed are not used in this application.
2.
A single value in a column means that the value is the same in English units and in SI
units.
3.
Point numbers that appear in bold type (e.g. 03) can be unbundled at the field panel.
Table 15 APOGEE FLN P1 Application 2721 Point Number Summary
Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Parameter
01
LAO
CTLR ADDRESS
31
-
1
0
-
-
F6-78
02
LAO
APPLICATION
-
-
1
0
-
-
-
03
LAI
FREQ OUTPUT
0
Hz
0.01
0
-
-
U1-02
04
LAI
PCT OUTPUT
0
%
0.01
0
-
-
-
05
LAI
SPEED
0
RPM
1
0
-
-
-
06
LAI
CURRENT
0
A
0.01
0
-
-
U1-03
07
LAI
TORQUE
0
%
0.1
0
-
-
U1-09
08
LAI
POWER
0
kW
0.1
0
-
-
U1-08
09
LAI
DRIVE TEMP
0
° C/F
1
0
-
-
U4-08
10
LAI
DRIVE KWH
0
kWh
0.1
0
-
-
U4-10
11
LAI
MWH
0
MWh
1
0
-
-
U4-11
12
LAI
RUN TIME
0
h
1
0
-
-
U4-01
13
LAI
DC BUS VOLT
0
V
1
0
-
-
U1-07
14
LAI
AC OUT VOLT
0
V
0.1
0
-
-
U1-06
15
LAI
PAR N9.01
0
A
0.01
0
-
-
n9-01
16
LAI
RUN TIMEX10K
0
10Kh
1
0
-
-
U4-01
17
LAI
FAULT CODE
0
-
1
0
-
-
U2-01
18
LDI
MINOR FLT
NO FLT
-
1
0
FAULT
NO FLT
U1-12
(Bit 6)
19
LDI
MAJOR FLT
NO FLT
-
1
0
FAULT
NO FLT
U1-12
(Bit 7)
20
LAO
OVRD TIME
1
h
1
0
-
-
-
21
LDI
FWD.REV
FWD
-
1
0
REV
FWD
U1-12
(Bit 2)
22
LDO
CMD REV.STOP
STOP
-
1
0
REV
STOP
-
23
LDI
RUN.STOP
STOP
-
1
0
RUN
STOP
U1-12
(Bit 0)
24
LDO
CMD RUN.STOP
STOP
-
1
0
FWD
STOP
-
10 APOGEE FLN P1 Communications
YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual
39