Network Drive Operations

The drive operations that can be performed by Metasys N2 or APOGEE FLN P1

communication depend on drive parameter settings. This section explains the functions that

can be used and related parameter settings.

u

Observing the Drive Operation

A controller can perform the following actions with network communications at any time

regardless of parameter settings:
• observe drive status and drive control terminal status from a controller
• read and write parameters
• set and reset faults
• set multi-function inputs.

Note:

Input settings from the input terminals So and from network communications are both linked by a logical

OR operation.

u

Controlling the Drive

Select an external reference and adjust the parameters in

Table 8

accordingly to start and stop

the drive or set the frequency reference using Metasys N2 or APOGEE FLN P1

communications.

Table 8 Setting Parameters for Drive Control from Metasys N2 or APOGEE FLN P1

Reference Source

Parameter

Name

Required Setting

External Reference 1

b1-01

Frequency Reference Selection 1

3

b1-02

Run Command Selection 1

3

External Reference 2

b1-15

Frequency Reference Selection 2

3

b1-16

Run Command Selection 2

3

7 Network Drive Operations

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual