beautypg.com

Metasys n2 analog output (ao) summary, 9 metasys n2 communications – Yaskawa APOGEE FLN P1 User Manual

Page 30

background image

Object ID

Object Name

Units

Yaskawa Drive Parameter

AI 20

Freq Ref @ Fault

0.01 Hz

U2-03

AI 21

Output Freq @ Fault

0.01 Hz

U2-04

AI 22

Output Current @ Fault

0.1 A

U2-05

AI 23

Out Volt Ref @ Fault

0.1 Vac

U2-07

AI 24

DC Bus Volts @ Fault

1 Vdc

U2-08

AI 25

Output Power @ Fault

0.1 kW

U2-09

AI 26

Input Term Status @ Fault

-

U2-11

AI 27

Output Term Status @ Fault

-

U2-12

AI 28

Operation Status @ Fault

-

U2-13

AI 29

Elapsed Operation Time @ Fault

1 hour

U2-14

AI 30

Most Recent Fault

-

U3-01

AI 31

2nd Most Recent Fault

-

U3-02

AI 32

3rd Most Recent Fault

-

U3-03

AI 33

4th Most Recent Fault

-

U3-04

AI 34

Elapsed Time @ Current Fault

1 hour

U3-11

AI 35

Elapsed Time @ 2nd Fault

1 hour

U3-12

AI 36

Elapsed Time @ 3rd Fault

1 hour

U3-13

AI 37

Elapsed Time @ 4th Fault

1 hour

U3-14

AI 38

Read Parameter Data

-

-

n

Metasys N2 Analog Output (AO) Summary

Table 11 Metasys N2 Analog Output Summary ( Metasys N2 to SI-J3)

Object

ID

Object Name

Units

Default Value

Yaskawa Drive

Parameter

AO 1

Speed Command

0.01 Hz

-

-

AO 2

Acceleration Time

seconds

30.0

C1-01

AO 3

Deceleration Time

seconds

30.0

C1-02

AO 4

PI Proportional Gain

-

2.00

b5-02

AO 5

PI Integral Time

seconds

5.0

b5-03

AO 6

Stall Prevention Level – Run

%

120

L3-06

AO 7

Stall Prevention Level – Accel

%

120

L3-02

AO 8

Reference Operation Mode Select

-

1

b1-01

AO 9

Run Operation Mode Select

-

1

b1-02

AO 10

PI Mode Select

-

0

b5-01

AO 11

Frequency Command Upper Limit

% of Max

100.0

d2-01

AO 12

Frequency Command Lower Limit

% of Max

0.0

d2-02

9 Metasys N2 Communications

30