Metasys n2 analog output (ao) summary, 9 metasys n2 communications – Yaskawa APOGEE FLN P1 User Manual
Page 30
Object ID
Object Name
Units
Yaskawa Drive Parameter
AI 20
Freq Ref @ Fault
0.01 Hz
U2-03
AI 21
Output Freq @ Fault
0.01 Hz
U2-04
AI 22
Output Current @ Fault
0.1 A
U2-05
AI 23
Out Volt Ref @ Fault
0.1 Vac
U2-07
AI 24
DC Bus Volts @ Fault
1 Vdc
U2-08
AI 25
Output Power @ Fault
0.1 kW
U2-09
AI 26
Input Term Status @ Fault
-
U2-11
AI 27
Output Term Status @ Fault
-
U2-12
AI 28
Operation Status @ Fault
-
U2-13
AI 29
Elapsed Operation Time @ Fault
1 hour
U2-14
AI 30
Most Recent Fault
-
U3-01
AI 31
2nd Most Recent Fault
-
U3-02
AI 32
3rd Most Recent Fault
-
U3-03
AI 33
4th Most Recent Fault
-
U3-04
AI 34
Elapsed Time @ Current Fault
1 hour
U3-11
AI 35
Elapsed Time @ 2nd Fault
1 hour
U3-12
AI 36
Elapsed Time @ 3rd Fault
1 hour
U3-13
AI 37
Elapsed Time @ 4th Fault
1 hour
U3-14
AI 38
Read Parameter Data
-
-
n
Metasys N2 Analog Output (AO) Summary
Table 11 Metasys N2 Analog Output Summary ( Metasys N2 to SI-J3)
Object
ID
Object Name
Units
Default Value
Yaskawa Drive
Parameter
AO 1
Speed Command
0.01 Hz
-
-
AO 2
Acceleration Time
seconds
30.0
C1-01
AO 3
Deceleration Time
seconds
30.0
C1-02
AO 4
PI Proportional Gain
-
2.00
b5-02
AO 5
PI Integral Time
seconds
5.0
b5-03
AO 6
Stall Prevention Level – Run
%
120
L3-06
AO 7
Stall Prevention Level – Accel
%
120
L3-02
AO 8
Reference Operation Mode Select
-
1
b1-01
AO 9
Run Operation Mode Select
-
1
b1-02
AO 10
PI Mode Select
-
0
b5-01
AO 11
Frequency Command Upper Limit
% of Max
100.0
d2-01
AO 12
Frequency Command Lower Limit
% of Max
0.0
d2-02
9 Metasys N2 Communications
30