n

Change Directions

CMD REV.STOP (Point 22) can be commanded to run the drive in the reverse direction.

FWD.REV (Point 21) shows the current direction of the drive rotation.

NOTICE: Damage to Equipment. Improper drive direction may damage HVAC equipment if parameter b1-04,

Reverse Enable, is improperly set (b1-04=0). Confirm proper motor rotation prior to connecting the load to

the motor.

n

Lock the Drive Panel

Locking the panel prevents the user from using the LOCAL/REMOTE and STOP keys locally

at the drive panel. LOCK PANEL (Point 33) can be commanded to lock and unlock the panel.

n

Digital Outputs

MULTI OUT 1 (Point 40), MULTI OUT 2 (Point 41), and MULTI OUT 3 (Point 42) are

physical digital outputs on the drive. Their purpose depends on how the drive has been set-

up. The drive can be programmed so that these points can display various limits, warnings,

and status conditions. Some examples include frequency limit, over current, and motor over

temperature fault.

n

Loop Gain

PID P GAIN (Point 63) and PID I TIME (Point 64) are the gain and integral time parameters

similar to the P and I gains in the APOGEE FLN Terminal Equipment Controllers. The PI

loop of the drive is structured differently than the Siemens loop, so there is not a one-to-one

correspondence between the gains.

n

Reading and Resetting Faults

OK.FAULT (Point 93) shows the current status of the drive. FAULT CODE (Point 17)

contains the code for the most current fault. LST FLT CODE (Point 66) contains the code for

the previous fault.

Refer to APOGEE FLN P1 Application 2721 Point Number Summary

on page 39

for descriptions of the fault codes. The drive can be reset back to OK mode by

commanding RESET FAULT (Point 94) to RESET. The RESET FAULT command is only

available when the CMD RUN.STOP (Point 24) and CMD REV.STOP (Point 22) are both

STOP.

u

APOGEE FLN Point Database

This section shows the APOGEE FLN point database for Application 2721.

n

APOGEE FLN Point List Summary

This database is for APOGEE FLN Application 2721 and features logical points: Logical

Analog Inputs (LAI), Logical Analog Outputs (LAO), Logical Digital Inputs (LDI) and

Logical Digital Outputs (LDO). These points configure, control or monitor the operation of

the drive.

10 APOGEE FLN P1 Communications

38

YASKAWA TOEP YAICOM 13 Metasys N2 & Apogee FLN P1 SI-J3 Installation & Technical Manual