Digital Operator

Display

Alarm Name

R-DNE-So

(Rdd)

Remote Drive Disable

SE

MEMOBUS/Modbus Communication Test Mode Error

Note:

This alarm will not trigger a multi-function output terminal that is set for alarm output

(H2-oo = 10).

TdE

Time Data Error

TrPC

IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.

UL3

Undertorque Detection 1
The current has fallen below the minimum value set for Torque Detection Level 1 (L6-02) for longer than the allowable time

(L6-03).

UL4

Undertorque Detection 2
The current has fallen below the minimum value set for Torque Detection Level 2 (L6-05) for longer than the allowable time

(L6-06).

UL6

Underload Det 6

Motor Underload
The load has fallen below the underload curve defined in L6-14.

Uv

Control Circuit Undervoltage
One of the following conditions occurred:
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage is under L2-05.

u

Operator Programming Errors

n

oPE Codes

An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an

inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not

trigger an alarm or fault output. When an oPE appears on the operator display, press the ENTER button to view U1-18 and

see which parameter is causing the oPE.

Digital Operator

Display

Error Name

oPE01

Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.

oPE02

Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.

oPE03

Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-07.

oPE04

Initialization Required, Term <–> Ctrl Chg

oPE05

Run Command/Frequency Reference Source Selection Error

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-06 and PID functions conflict.

oPE08

Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.

oPE09

PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1).

oPE10

V/f Data Setting Error
One of the following setting errors has occurred:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

oPE33

Net Incompatible

Parameter selection is incompatible with the selected network P9-99

i.7 Troubleshooting

84