Table i.23 Multi Setpoints 1 and 2
Multi Setpoint 1
(H1-0o = 8D)
Multi Setpoint 2
(H1-0o = 8E)
Setpoint Source
Open
Open
Frequency Ref (dependent on b1-01), Set-Point 1
- Q1-01 (when b1-01 = 0), Analog Setpoint
(H3-0o = C), Pulse Input Setpoint (H6-01 = 2),
or Memobus setpoint.
Closed
Open
Set Point 2 – Q1-02
Open
Closed
Set Point 3 – Q1-03
Closed
Closed
Set Point 4 – Q1-04
n
H2-01 to H2-03: Terminal MA/MB/MC, P1/PC, and P2/PC Function Selection
The drive has three multi-function output terminals.
No.
Parameter Name
Setting Range
Default
H2-01
Terminal MA, MB and MC Function Selection (relay)
0 to 1AA
E: Fault
H2-02
Terminal P1 Function Selection (open-collector)
0 to 1AA
37: During Frequency Output
H2-03
Terminal P2 Function Selection (open-collector)
0 to 1AA
E: Fault
Setting E: Fault
The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Setting 37: During Frequency Output
The output closes when the drive is outputting a frequency.
Status
Description
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed
Drive is outputting frequency.
ON
ON
OFF
OFF
ON
OFF
ON
run command
baseblock
command
output
frequency
during run
during frequency
output
OFF
Figure i.41 During Frequency Output Time Chart
n
P1-01: Pump Mode
Selects the base operation mode of the drive controller.
No.
Parameter Name
Setting Range
Default
P1-01
Pump Mode
0, 3
0
Setting 0: Drive only
Designed for single pump stand-alone applications
Setting 3: MEMOBUS network
Up to eight drives can be networked together to provide for system redundancy and precise control.
Staging is disabled when and the drive PID output is influenced by the Water Level / Suction Pressure Control.
The functions listed below will behave slightly different when P1-01 is set to 3:
• Start Level: Active on the first pump in the network. Drives in the process of alternation will not undergo this process.
• Sleep: Active when the drive is the only drive running on the network.
i.6 Start-Up Programming and Operation
76