Menu structure for digital led operator, Powering up the drive, 1> reverse can only be selected when local is set – Yaskawa iQpump Micro Quick Start User Manual
Page 59: I.6 start-up programming and operation, Programming mode drive mode

No.
Display
Name
Function
16
–
Communication Port
Port used for USB Copy Unit, LCD Operator Keypad, and for connecting to a PC.
NOTICE: Use only specified cable when making connections to the drive. Failure
to comply may damage the drive.
NOTICE: Do not open the port cover wider than 90 degrees. Failure to comply
may break the port cover and leave the unprotected port susceptible to damage.
u
Menu Structure for Digital LED Operator
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
X
:
:
:
:
Turn the power on
Forward Selection
Reverse Selection
Output Frequency
Output Current
Output Voltage
Monitor Display
Verify Menu
Set Up Mode
Parameter Setting Mode
Auto-Tuning
Description of Key Operations
Note: “XX” characters are shown in this manual.
The drive will display the actual setting values.
PROGRAMMING MODE
DRIVE MODE
<1>
Application Preset
Figure i.24 Digital LED Operator Screen Structure
<1> Reverse can only be selected when LOCAL is set.
n
Powering Up the Drive
Review the following checklist before turning the power on.
Item to Check
Description
Power supply voltage
Ensure the power supply voltage is correct:
200 V class: single-phase 200 to 240 Vac 50/60 Hz
200 V class: 3-phase 200 to 240 Vac 50/60 Hz
400 V class: 3-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
(for single-phase 200 V class models, wire only R/L1 and S/L2)
Check for proper grounding of drive and motor.
Drive output terminals
and motor terminals
Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.
Control circuit terminals
Check control circuit terminal connections.
Drive control terminal status
Open all control circuit terminals (off).
Status of the load
and connected machinery
Uncouple the motor from the load.
i.6 Start-Up Programming and Operation
YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide
59