i.5

Main Circuit Wiring

This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit of

the drive.

NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices

could result in drive malfunction due to loose terminal connections.

u

Main Circuit Terminal Functions

Table i.2 Main Circuit Terminal Functions

Terminal

Type

Function

Reference

R/L1

Main circuit power supply

input

Connects line power to the drive.

Drives with single-phase 200 V input power use terminals R/L1 and S/L2 only.

Do NOT use T/L3.

S/L2
T/L3

U/T1

Drive output

Connects to the motor.

49

V/T2

W/T3

B1

Braking resistor

Available for connecting a braking resistor or the braking resistor unit option.

B2

⊕1

DC link choke connection These terminals are shorted at shipment. Remove the shorting bar between ⊕1

and

⊕2 when connecting a DC link choke to this terminal.

⊕2
⊕1

DC power supply input

For connecting a DC power supply.

(2 terminals)

Ground

Grounding Terminal

49

u

Wire Gauges and Tightening Torques

Select the appropriate wires and crimp terminals from

Table i.3

through

Table i.5

.

Note:

1. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient

temperature within 30 °C and wiring distance shorter than 100 m.

2. Terminals

⊕1, ⊕2, ⊖, B1 and B2 are for connecting optional devices such as a braking resistor. Do not connect other non-specified

devices to these terminals.

• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater

than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to

calculate the amount of voltage drop:

• Line drop voltage (V) = 3 x wire resistance (Ω/km) x wire length (m) x current (A) x 10

-3

• Refer to instruction manual TOBP C720600 00 for braking unit or braking resistor unit wire gauges.

Refer to UL Standards Compliance on page 102

for information on UL compliance.

n

Single-Phase 200 V Class

Table i.3 Wire Gauge and Torque Specifications

Drive

Model

Terminal

Recomm.

Gauge

AWG, kcmil

Wire Range
AWG, kcmil

Screw

Size

Tightening

Torque

N•m (lb.in.)

BV0006

R/L1, S/L2, T/L3

12

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

BV0010

R/L1, S/L2, T/L3

10

14 to 10

M4

1.2 to 1.5

(10.6 to 13.3)

U/T1, V/T2, W/T3

14

14 to 10

⊖, ⊕1, ⊕2

14 to 10

B1, B2

14 to 10

10

14 to 10

i.5 Main Circuit Wiring

46

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide