I.5 main circuit wiring – Yaskawa iQpump Micro Quick Start User Manual
Page 57

No.
Item
Page
13
Set up overload protection circuits when running multiple motors from a single drive.
M1
OL1
OL2
OLn
MC1
MC2
MCn
M2
Mn
Drive
MC1 - MCn
OL 1 - OL n
... magnetic contactor
... thermal relay
Power supply
Note: Close MC1 through MCn before operating the drive.
–
14
If using a braking resistor or dynamic braking resistor unit, install a magnetic contactor. Properly install the resistor,
and ensure that overload protection shuts off the power supply.
–
15
Verify phase advancing capacitors are NOT installed on the output side of the drive.
–
Control circuit wiring
16
Use twisted-pair cables for all drive control circuit wiring.
–
17
Ground the shields of shielded wiring to the GND terminal.
18
If using a 3-Wire sequence, set parameters for MFDI terminals S1 through S7, and properly wire control circuits.
19
Check for any other wiring mistakes. Only use a multimeter to check wiring.
–
20
Properly fasten the control circuit terminal screws in the drive. Refer to
21
Pick up all wire clippings.
–
22
Ensure that no frayed wires on the terminal block are touching other terminals or connections.
–
23
Properly separate control circuit wiring and main circuit wiring.
–
24
Analog signal line wiring should not exceed 50 m.
–
25
Safe Disable Input wiring should not exceed 30 m.
–
i.5 Main Circuit Wiring
YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide