Digital Operator
Display
Alarm Name
High Feedback High FB
Sensed
(HIFB)
High Feedback Level Alarm
The feedback signal is too high.
LOP
Loss of Prime
The pump has lost its prime and P1-22 is set to 1.
Low City Pressure
(LCP)
Low City Pressure
Low Feedback Low FB
Sensed
(LoFb)
Low Feedback Level Alarm
The feedback signal is too low.
Low Suction Pressure
(LSP)
Low Suction Pressure
Low Water in Tank
(LWT)
Low Water in Tank
LT-1
Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.
Note:
An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and
H2-oo = 10) are set.
LT-2
Capacitor Maintenance Time
The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
LT-3
Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
LT-4
IGBT Maintenance Time (50%)
IGBTs have reached 50% of their expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
NETSCAN
Waiting for Master
(NETSC)
NETSCAN
Drive is waiting for a message from the master.
NMS
(NOTSP)
Not Maintaining Setpoint
The setpoint cannot be maintained and P1-17 is set to 1.
oH
Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02.
oH2
Heatsink Overheat Warning
“Heatsink Overheat Warning” was input to a multi-function input terminal, S1 through S7 (H1-oo= B).
oH3
Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02 or H3-10 = E).
oL1
Motor Overload
The electronic motor overload protection tripped
oL2
Drive Overload
The thermal sensor of the drive triggered overload protection.
oL3
Overtorque Detection 1
The current has exceeded the value set for Torque Detection Level 1 (L6-02) for longer than the allowable time (L6-03).
oL4
Overtorque Detection 2
The current has exceeded the value set for Torque Detection Level 2 (L6-05) for longer than the allowable time (L6-06).
ov
Control Circuit Overvoltage
Voltage in the control circuit exceeded the trip point.
• For 200 V class drives: approximately 410 V
• For 400 V class drives: approximately 820 V (740 V when E1-01 < 400)
PCyC
Pump Over Cycle
i.7 Troubleshooting