Status (param01), Called station # (param02), Function code (param04) – Yaskawa Ladder Works Programming Manual User Manual
Page 201: Data address (param05), Data size (param06), Called cpu # (param07), Coil offset (param08)

9.8 Receive Message Function (MSG-RCV)
9-26
■ Status (PARAM01)
Output the status of the transmission unit. See 5.5.1."Parameters" of "Status (PARAM01)" for
details.
■ Called Station # (PARAM02)
The station number of sending side is output.
■ Function Code (PARAM04)
Output the MEMOBUS function code received. Refer to Table 9.13.
Table 9.13 Function Codes
Function Code
Setting
00H Unused
×
01H
Read coil status
○
02H
Read input relay status
○
03H
Read contents of holding register
○
04H
Read contents of input register
○
05H
Change status of single coil
○
06H
Write into a single holding register
○
07H Unused
×
08H Loop-back
test
○
09H
Read contents of holding register (expanded)
○
0AH
Read contents of input register (expanded)
○
0BH
Write into holding register (expanded)
○
0CH Unused
×
0DH
Discontinuous readout of holding register (expanded)
○
0EH
Discontinuous write into holding register (expanded)
○
0FH
Change status of a multiple coil
○
10H
Write into a plurality of holding register
○
11H to 20H
Unused
×
21H to 3FH
System reserved
×
40H to 4FH
System reserved
×
50H to
Unused
×
Note : The MB, MW, IB, and IW registers can be used respectively as the coil, holding register,
input relay, and input registers during slave operation.
■ Data Address (PARAM05)
The data address requested by the sending side is output.
■ Data Size (PARAM06)
The data size (number of bits or number of words) of the requested read or write is output.
■ Called CPU # (PARAM07)
The called CPU NO. is output.
■ Coil Offset (PARAM08)
Set the offset word address of the coil. This is valid in the case of function codes 01H, 05H, and
0FH.