Called station # (param02), Function code (param04) – Yaskawa Ladder Works Programming Manual User Manual
Page 193

9.7 Send Message Function (MSG-SND)
9-18
REQUEST
1 = Request
0 = Completion of receipt report
■ Called Station # (PARAM02)
Serial
1~254 : Message is sent to the station of designated device address.
■ Function Code (PARAM04)
The MEMOBUS function code to be sent is set. Refer to Table 9.9.
Table 9.9 Function Codes
Function Code
Setting
00H Unused
×
01H
Read coil status
○
02H
Read input relay status
○
03H
Read contents of holding register
○
04H
Read contents of input register
○
05H
Change status of single coil
○
06H
Write into a single holding register
○
07H Unused
×
08H Loop-back
test
○
09H
Read contents of holding register (expanded)
○
0AH
Read contents of input register (expanded)
○
0BH
Write into holding register (expanded)
○
0CH Unused
×
0DH
Discontinuous readout of holding register (expanded)
○
0EH
Discontinuous write into holding register (expanded)
○
0FH
Change status of a multiple coil
○
10H
Write into a plurality of holding register
○
11H to 20H
Unused
×
21H to 3FH
System reserved
×
40H to 4FH
System reserved
×
50H to
Unused
×
(× : cannot be set, ○ :can be set)
Note : Only MW (MB) can be used as the sending/receiving register during master operation. The
MB, MW, IB, and IW registers can be used respectively as the coil, holding register, input