7.2 DEAD ZONE B Instruction (DZB)
7-4
7.2 DEAD ZONE B Instruction (DZB)
[Outline]
The DZB instruction executes a dead zone operation on integer, double-length integer or real number
data.
The following operation is performed, where Input is the input value, Zone is the designated dead zone
value, and Output is the output value:
•
Output = Input – the absolute value of Zone (the absolute value of Input is greater than or equal
to the absolute value of Zone; Input is greater than or equal to 0)
•
Output = Input + the absolute value of Zone (the absolute value of Input is greater than or equal
to the absolute value of Zone; Input is less than or equal to 0)
•
Output = 0 (the absolute value of Input is less than the absolute value of Zone)
+D
-D
X
Y
[Format]
Symbol : DZB
Full Name : Dead Zone B
Category : DDC
Icon :
[Parameter]
Parameter Name
Setting
Input
· Any integer type, double-length integer type and real number type register
· Any integer type, double-length integer type and real number type register
with subscript
· Subscript register
· Constant
Zone
· Any integer type, double-length integer type and real number type register
· Any integer type, double-length integer type and real number type register
with subscript
· Subscript register
· Constant
Output
· Any integer type, double-length integer type and real number type register
(except for # and C registers)
· Any integer type, double-length integer type and real number type register
with subscript (except for # and C registers)
· Subscript register