7 send message function (msg-snd) – Yaskawa Ladder Works Programming Manual User Manual
Page 190
9.7 Send Message Function (MSG-SND)
9-15
9.7 Send Message Function (MSG-SND)
[Outline]
Sends a message to the called station which is on the line and which is designated by the transmission
device type. Supports a plurality of protocol types.
The execution command (Execute) must be held until Complete or Error becomes ON.
[Transmission Devices ] CPU Module, 215IF, 217IF, 218IF, SV-01
[Protocols] MEMOBUS, non-procedural
[Format]
Symbol : MSG-SND
Full Name : Message Send
Category : SYSTEM
Icon :
[Parameter]
I/O
Definition
Parameter Name
I/O
Designation
Setting
Execute
B-VAL
Send message command
Abort
B-VAL
Send message forced interruption command
Type of transmission device
Dev-Typ I-REG
CPU module = 8
218IF = 6
215IF = 1
SVB-01 = 11
217IF = 5
Pro-Typ I-REG
Transmission
protocol
MEMOBUS = 1
non-procedural = 2
Line No.
Cir-No I-REG
CPU module = 1, 2
218IF = 1 to 8
215IF = 1 to 8
SVB-01 = 1 to 16
217IF = 1 to 24
Transmission buffer channel No.
Ch-No I-REG
CPU module=1, 2
218IF = 1 to 10
215IF = 1 to 13
SVB-01 = 1 to 8
217IF = 1
Input
Param
Address input
Head address of set data (MW, DW, #W)
Busy
B-VAL
Message is being sent.
Complete
B-VAL
The sending of the message has been completed.
Output
Error
B-VAL
Occurrence of error