9.8 Receive Message Function (MSG-RCV)
9-25
9.8.1 Parameters
They adhere to contents-functions and so on and are collected into parameter numerical order.
Table 9.12 is Parameter List.
Table 9.12 Parameter List
Contents
Parameter No.
IN/OUT
MEMOBUS Non-procedural
PARAM 00
OUT
Process result
Process result
PARAM 01
OUT
Status
Status
PARAM 02
OUT
Called station #
Called station #
PARAM 03
SYS
System reserved
System reserved
PARAM 04
OUT
Function code
PARAM 05
OUT
Data address
Data address
PARAM 06
OUT
Data size
Data size
PARAM 07
OUT
Called CPU#
Called CPU#
PARAM 08
IN
Coil offset
PARAM 09
IN
Input relay offset
PARAM 10
IN
Input register offset
PARAM 11
IN
Holding register offset
Register offset
PARAM 12
IN
Write-in range LO
Register offset
PARAM 13
IN
Write-in range HI
Register offset
PARAM 14
SYS
For system use
For system use
PARAM 15
SYS
System reserved
System reserved
PARAM 16
SYS
System reserved
System reserved
■ Process Result (PARAM00)
The process result is output to the upper byte. The lower byte is for system analysis.
•
00xx : In process (BUSY)
•
10xx : End of process (COMPLETE)
•
8xxx : Occurrence of error (ERROR)
Error Classification
•
81xx : Function cord error
The sending of an unused function code was attempted. Or, an unused function code was
received.
•
82xx : Address setting error
The data address, coil offset, input relay offset, input register offset, or holding register
offset setting is out of range.
•
83xx : Data size error
The size of the sent or received data is out of range.
•
84xx : Line No. setting error
The line No. setting is out of range.
•
85xx : Channel No. Setting error
The channel No. setting error.
•
86xx : Station address error
The station No. setting is out of range.
•
88xx : Transmission unit error
An error response was returned from the transmission unit. (Refer to 5.6.1)
•
89xx : Device selection error
A non-applicable device is selected.