beautypg.com

4 power supply to converter unit, Figure 2.1.4.2 connection between devices, 20 a 0.53 mh – Yaskawa YASNAC PC NC Connecting Manual User Manual

Page 38: X 002491), X 010057), 30 a 0.35 mh, X 002492), X 010058), 40 a 0.265 mh, X 002493)

background image

2 - 4

YASNAC PCNC Connecting Manual

Chapter 2: Power Supply

2.1.4

Power Supply to Converter Unit

*Note: Code in upper row: with leads

Code in lower row : with terminals

Table 2.1.4.2 Component Selection for Power Supply Circuit

Converter

Type CIMR-

MR5N2

ooo

Applicable

Capacity

(kW)

Output

Capacity

(kW)

Power

Source

Capacity

(KVA)

Breaker

1MCCB

Electro-

magnetic

Contactor

1MC

Reator*

1L

3P7

3.7

4.6

7

30A

20A

20 A 0.53 mH

(x 002491)
(x 010057)

5P5

5.5

6.8

9

40A

30A

30 A 0.35 mH

(x 002492)
(x 010058)

7P5

7.5

9.3

12

50A

40A

40 A 0.265 mH

(x 002493)
(x 010059)

011

11

13.6

19

75A

60A

60 A 0.18 mH

(x 002495)
(x 010060)

015

15

18.6

24

100A

75A

80 A 0.13 mH

(x 002497)
(x 010061)

018

18.5

22.9

30

125A

100A

90 A 0.12 mH

(x 002498)
(x 010062)

022

22

27.2

36

150A

125A

120 A 0.09 mH

(x 002555)
(x 010063)

030

30

37.1

48

175A

150A

160 A 0.07 mH

(x 002556)
(x 010064)

Converter unit

CIMR-MR5

Power supply

L

MC

TXR

MCCB

FIGURE 2.1.4.2 Connection between Devices