10 Technical Data

SMA Solar Technology AG

58

AS-BOX-M_L-IA-IEN110320

Installation Guide

Load connection

Consumption meter connection

Nominal power at 35 °C

35 kW

Nominal current with grid operation per phase at 35 °C

50 A

Power for 30 minutes at 35 °C

41 kW

Current for 30 minutes at 35 °C

50 A

Maximum cross-section of the insulated conductor to be
connected

16 mm²

Stripping length of the insulated conductors

18 mm … 20 mm

Maximum fuse link to be used

D02

Maximum rated current of the fuse link

63 A

Nominal power at 35 °C

35 kW

Nominal current per phase at 35 °C

50 A

Power for 30 minutes at 35 °C

41 kW

Current for 30 minutes at 35 °C

50 A

Maximum cross-section of the insulated conductor to be
connected

16 mm²

Stripping length of the insulated conductors

18 mm … 20 mm

Maximum rated short-circuit current

10 kA

Maximum nominal current of the back-up fuse

63 A

Short-circuit current switch-off capability of the back-up
fuse

≥ 25 kA

Cut-off current of back-up fuse

≤ 17 kA