SMA Solar Technology AG

5 Electrical Connection

Installation Guide

AS-BOX-M_L-IA-IEN110320

33

5.5 Connecting Loads

Overcurrent protective device and switch-disconnector:
During stand-alone grid operation, the Sunny Backup and the PV plant supply the loads. This disables
the fuse on the grid side. During stand-alone grid operation, the fuse-switch-disconnector "AS-F5"
protects the loads' cables against overload.

Requirements for the residual current device in the TT system:

☐ The nominal tripping current is 100 mA maximum.
☐ Secure tripping with several residual current devices is provided if

g x ΣI

ΔN

≤ 100 mA.

g = coincidence factor of the residual current devices
ΣI

ΔN

= total of nominal tripping currents of the residual current devices

Coincidence factor
g = 1 corresponds to 1 residual current device in the system.
g = 0.5 corresponds to 2 ... 4 residual current devices in the system.
g = 0.35 corresponds to 5 ... 10 residual current devices in the system.
g = 0.25 corresponds to > 10 residual current devices in the system.

Risk of lethal electric shock in the TT system without personal protection.

• Install residual current devices between the Backup system and the loads' electric circuit.