7 Disconnecting the Automatic Switch Box from voltage sources

Installation Guide

AS-BOX-M_L-IA-IEN110320

49

7 Disconnecting the Automatic Switch Box from voltage

sources

1. Decommission the Backup system (see the manual of the Sunny Backup 5000).
2. Switch off the line fuse between feed-in meter and Automatic Switch Box and between

consumption meter and Automatic Switch Box and secure against re-connection.

3. Switch off the line circuit breaker/residual current device between the PV plant and the

Automatic Switch Box and secure against re-connection.

4. Open the Automatic Switch Box with the switch cabinet key.
5. Switch off the line circuit breaker "AS-F1", the residual current device "AS-Q8" and the fuse-

switch-disconnector "F6 (Generator)" in the Automatic Switch Box.

6. Ensure that no voltage is present.
7. Cover or shield any adjacent voltage-carrying parts.