5.10 Connecting External Signal for Battery Feed-In

By connecting a potential-free contact to the Automatic Switch Box, you can start or stop grid feed-in
from the battery. You can connect for example a relay output of a ripple control receiver to the
terminal strip "AS-X7/ Feed in Signal" which receives signals from the network operator.

Requirements:

☐ The cross-section of the insulated conductor is 2.5 mm² maximum.
☐ The potential-free contact is suited for a grid voltage of 230 V.

Connection terminals:

1. Insert the cable (see section 5.2).
2. Connect PE to terminal strip "AS-X7/ Feed in Signal". Take the labeling on the connection

terminals into account.

3. Connect the remaining insulated conductors to connection terminals "In" and "L1" of the terminal

strip "AS-X7/ Feed in Signal".

Approval from the network operator

The responsible network operator must approve feed-in from the battery into the power
distribution grid.

Displayed graphic

As an example, only the Automatic Switch Box L will be graphically displayed in this section.
The labeling of the connection terminals as well as the procedure for connecting the
Automatic Switch Box M is identical.