Error number

Display message, cause and corrective measures

9310

Signal fault in battery system > Check battery connection
The connection between the Battery Pack and the inverter is disrupted.
Corrective measures:

• Ensure that the power cable and the data cable are properly

connected to the Battery Pack (see inverter manual at www.SMA-
Solar.com).

• Ensure that the plug contacts of the power cable and the data cable

are not damaged.

9311

Battery cell overvoltage fault
The voltage of at least one cell is outside the threshold.
Corrective measures:

• Immediately disconnect the inverter from all voltage sources (see

Section 2.3, page 8).

• Contact the SMA Service Line.

9312

Battery cell undervoltage fault
The cause must be determined by the SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.

9313

Low temperature fault in battery > Check installation site
The ambient temperature is below the lowest permitted temperature. The
inverter and the Battery Pack must only be operated at ambient tempera-
tures from 0°C to 40°C.
Corrective measures:

• Ensure that the permitted ambient temperatures are complied with at

the installation site.

• If this message is displayed even though the permitted ambient

temperature is complied with, contact the SMA Service Line.

9314

Overtemperature fault in battery > Check installation site
The ambient temperature is above the highest permitted temperature. The
inverter and the Battery Pack must only be operated at ambient tempera-
tures from 0°C to 40°C.
Corrective measures:

• Ensure that the permitted ambient temperatures are complied with at

the installation site.

• If this message is displayed even though the permitted ambient

temperature is complied with, contact the SMA Service Line.

4 Troubleshooting

SMA Solar Technology AG

Service Manual

SB36-50SE-SG-en-10