Error number
Display message, cause and corrective measures
7105
Param. setting failed
Parameters could not be set using the memory card. The inverter contin-
ues to feed in.
Corrective measures:
• Ensure that the parameters are set correctly.
• Ensure that you have an SMA Grid Guard code.
7106
Update file defect.
Update file on the memory card is defective.
Corrective measures:
• Reformat the memory card.
• Re-save the files to the memory card.
7110
No update file
No update file has been found.
Corrective measures:
• Copy the update file to the memory card folder. Select the folder
\UPDATE.
7112
Update file copied
The update file was successfully copied to the memory of the inverter pro-
cessor.
7201 to 7202
Data stor. not poss.
Internal error. The inverter continues to feed into the utility grid.
Corrective measures:
• Contact the SMA Service Line.
7303
Update main CPU failed
The cause must be determined by the SMA Service Line.
Corrective measures:
• Contact the SMA Service Line.
7324
Wait for update conditions
The inverter has successfully completed the update.
7330
Condition test failed
The conditions of the update file used for the inverter settings (e.g. coun-
try data set, device type) are not fulfilled.
Corrective measures:
• Contact the SMA Service Line.