Error number
Display message, cause and corrective measures
701
Frequency not permitted > Check parameter
The power frequency is not within the permissible range. The inverter has
disconnected from the utility grid.
Corrective measures:
• If possible, check the power frequency and observe how often
fluctuations occur.
If fluctuations occur frequently and this message is displayed often,
contact the grid operator and request approval to change the
operating parameters of the inverter.
If the grid operator gives his approval, discuss any changes to the
operating parameters with the SMA Service Line.
801
Waiting for grid voltage > Grid failure > Check fuse
The AC cable is not correctly connected or the country data set is not cor-
rectly configured.
Corrective measures:
• Ensure that the AC cable is correctly connected (see inverter manual
at
• Ensure that the country data set has been configured correctly.
Check the setting of the rotary switches A and B or select the
operating parameter Set country standard and check the value.
• Check the fuse.
901
PE conn. missing > Check connection
The grounding conductor is not correctly connected.
Corrective measures:
• Ensure that the grounding conductor is correctly connected (see
1001
L / N swapped > Check connection
The connection of L and N is swapped.
Corrective measures:
• Ensure that L and N are correctly connected (see inverter manual at
1101
Installation fault > Check connection
A second line conductor is connected to N.
Corrective measures:
• Correct the AC connection (see inverter manual at
4 Troubleshooting