Installation Preparations

Requirements on Environment

MSR 20-1X routers are designed for indoor application. To ensure the normal operation and prolong

their service life, the installation site must meet the requirements mentioned in the following sections.

Requirements on Temperature and Humidity

To ensure the normal operation and prolong their service life, the temperature and humidity in the

equipment room shall maintain at a certain level. A long-term high relative humidity will quite likely result

in poor insulation performance, electric leakage, mechanical property change, and corrosion, while a

low relative humidity will result in looseness of fastening screws owing to shrinkage of insulation washers,

or electrostatic discharge (ESD), which may damage the CMOS circuit on the router. A high temperature
will speed up the aging of insulation materials, and thus will greatly lower the reliability of the router and

shorten the service life.

Table 12

lists the requirements on the temperature and humidity for MSR 20-1X routers.

Table 12 Temperature and humidity requirements in the equipment room

Temperature Relative

Humidity

0°C to 40°C (32°F to 104°F)

5% to 90% (noncondensing)

Requirements on Cleanness

Dust is harmful to the safe operation of the router. Dust on the chassis may result in static absorption,

causing poor contact between metal connectors or joints, which may not only shorten the service life of

the router, but also bring about communication failures. Especially under the condition of a low indoor

humidity, dust is easier to be absorbed.

Table 13

lists the requirements on the dust concentration and diameters in the equipment room.

Table 13 Limitation on dust concentration and diameters in the equipment room

Diameter (μm) 0.5

1

3

5

Concentration
(particle/m³)

1.4 × 10

7

7 × 10

5

2.4 × 10

5

1.3 × 10

5

Besides, the contents of salt, acid, and sulfide in equipment room shall be strictly restricted. Harmful

gases will accelerate the corrosion of metal parts and the aging of some parts.

Table 14

lists the

concentration limit of SO

2

, H

2

S, NH

3

and CI

2

in the equipment room.

Table 14 Concentration limit of some harmful gases in equipment room

Gas

Concentration limit (mg/m

3

)

SO

2

0.2

H

2

S 0.006