Super Systems 9120 with TS User Manual
Page 66
SSi 9120 Touchscreen Interface
4586 – 9120 With Touch Screen Interface
Page 66 of 80
Section 3 – 9120 Web Pages
The 9120 controller has a simple website that will display some of the information associated with
the 9120, including current PV values and setpoints, among others. The website can be accessed
by any computer that is on the same network as the 9120 – directly through a crossover Ethernet
cable, or on a local company network. To access the website, just type in the IP address of the
controller, not the Touchscreen, into an web browser’s address bar:
The main page will be displayed,
which will display the PVT values as
well as the current setpoints. The
name of the furnace (from
Furnace
Setup
menu) will be listed as well.
The buttons across the top and
bottom of the screen will allow
interaction with the specific item on
the 9120. No modifications can be
made from the main screen.
The Operator button will allow the user
to modify the PV setpoints, as well as
the manual % on the PV. To make any
changes, the user will have to enter the
supervisor or administrator web
passwords first (
Furnace Setup
menu).
Once the password has been entered,
select the option to modify – Setpoint
1, Setpoint 2, Output Pwr 1 (PV 1
control percent output), or Output
Pwr 2 (PV 2 control percent output)
– and enter the value in the “Value”
box.
Note – The security box will turn
green when the Set Value button is
pressed and the password is correct. If
it is not correct, the box will stay red
.
The Output Pwr 1 and Output Pwr 2
options can only be modified when the
furnace PV is set to Manual. To set the
PV to manual, click on the MAN 1 button for PV 1, or click on MAN 2 button for PV 2. Once the
change has been made, the buttons will change to AUTO 1 or AUTO 2, as well as change color
from red to green. The changes may take a few seconds to be updated on the screen.