Super Systems 9120 with TS User Manual
Page 44

SSi 9120 Touchscreen Interface
4586 – 9120 With Touch Screen Interface
Page 44 of 80
Section 2 – 9120 Configurator 2.0 Menus
Burnoff
When a probe is in a furnace,
soot will collect in the end of the
probe, which will have a negative
effect on the performance of the
probe. Burnoffs are used to
clean out the built-up carbon by
burning it off of the probe.
Burnoff
Clicking on this value allows
users to manually initiate burnoff
procedure. The user will have to
confirm this action
The “Test Status” will display the
status of the burnoff.
Cancel
Clicking on this value will manually shut off the burnoff test. The user will have to confirm this
action.
Next Burnoff In
This value is a displayed calculation based on the burnoff time set in the
Burnoff Setup
menu
option. It displays the number of minutes until the next burnoff will be automatically initiated.
Test Status
This value displays the current testing status. The list of possible values are: Burnoff, Burnoff
Recovery, or Idle.
Timer (sec)
This value shows the remaining time, in seconds, for the Burnoff.
MV
This value is a display of the current millivolt input value during a burnoff test.
TC
This value is a display of the current probe thermocouple input value during a burnoff test.
Start mV
This value is a display of the millivolt input value at the beginning of the Burnoff test.
Start TC
This value is a display of the probe thermocouple value at the beginning of the burnoff test.
Last Burnoff