Super Systems 9120 with TS User Manual
Page 49

SSi 9120 Touchscreen Interface
4586 – 9120 With Touch Screen Interface
Page 49 of 80
Switch Point PID 2 -> 3
This is the PID Switch Point field. The range is –999 to 9999.
Setpoint Lower Limit
This is the setpoint lower limit for the loop. The range is -999 to 9999.
Setpoint Upper Limit
This is the setpoint upper limit for the loop. The range is -999 to 9999.
*** For a list of the factory default settings for each PVT type, see
Appendix A – PID Loop
Factory Default Configurations
. ***
Furnace Setup
The Furnace Setup menu option is
an administrative access only
option. Do not make any
adjustments on this screen without
first contacting Super Systems Inc.
Date and Time
This option will display the current
date and time on the 9120 controller
only (not the local computer or the
touch screen, if applicable). From
this menu option, the user can
change the date/time
on the 9120
controller
.
Note - See the section
Appendix B – Changing the
Date/Time on the Touchscreen for
instructions on how to change the time on the Touchscreen
.
Furnace Name
This value will define the name of the furnace. Clicking on the “Value” column will bring up an
input box where the user can enter the furnace’s name.
PV1 Name
This value will define the name of the first process variable. Clicking on the “Value” column will
bring up an input box where the user can enter the PV’s name.
PV2 Name
This value will define the name of the second process variable. Clicking on the “Value” column
will bring up an input box where the user can enter the PV’s name.
PVT Type
The PVT type is the mode the device runs in (Carbon, Dewpoint, etc.). The mode selected
determines the calculations and scaling for the Process Variable. Any time this selection is