REMKO SV 261 User Manual

Page 21

background image

2. Remove the factory-fitted

protective caps and union
nuts on the connections.
These should be used during
installation.

3. Before flanging the refrigerant

pipes, ensure that the union nut
is fitted on the pipe.

4. Prepare the laid refrigerant

pipes as shown below (Figs
11+12).

5. Verify that the shape of the

flange is correct (Fig 13).

6. First connect and hand-tighten

the refrigerant connections
to ensure they are correctly
seated.

7. Now fully tighten the fittings

using 2 suitably sized open-
ended spanners. Use one
spanner to counter the force
when tightening the fitting
(Fig 14)

.


Only employ tools and compo-
nents suitable for refrigeration
applications.

NOTE

Flanging tool

12 Flanging the refrigerant pipe

Refrigerant pipe

Deburrer

11 Deburring the refrigerant pipe

13 Correct flange shape

8. Use insulation hoses which are

designed for this temperature
range and diffusion tight.

9. Lay the refrigerant pipes

from the indoor unit to the
outdoor component. Esnure the
fastenings are adequate and if
necessary, take appropriate oil
return measures!

10. Observe the permitted bending

radius for the refrigerant pipes
during installation. Never bend
a pipe twice in the same place.
Brittle pipes and potential
cracking are the consequences.

11. Use the wall or floor brackets

to fit the outdoor component
against structural parts
approved to support the static
load (refer to the installation
instructions for the brackets).

12. Ensure that structure-borne

sound is not transferred to parts
of the building. Use vibration

dampers to reduce the effects
of structure-borne sound!

13. Prepare the refrigerant pipe

for the outdoor component as
described above.

Supplementary

installation notes.

If the basic length of the

refrigerant pipe exceeds 5

m, add refrigerant when

commissioning the system

for the first time. See chapter

"Adding refrigerant".

Tighten with 1st open-ended

spanner

Counter

2nd open-ended

spanner

14 Tightening the fitting

Tightening

torque:

1 4

“ 15-20 Nm

3 8

“ 33-40 Nm

1 2

“ 50-60 Nm

5 8

“ 65-75 Nm

3 4

“ 95-105 Nm

Connections to adjacent room
and fresh air intake
The indoor unit has been designed
to allow the cooling of a second
room as well as the intake of fresh
air.

Installation instructions

Proceed as follows to make the
connections to a second room and
the fresh air intake:

1. Please note that the vaporiser

fins are located directly behind
the cover being removed.
These should not be damaged
under any circumstances
(Page 22, Fig 8)

.

21