5 Installation inside buildings

Installation inside buildings

Ensure there is adequate heat
dissipation when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(Fig 5)

.

Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room.
This is used in conjunction with
ventilation ducts to compensate
any pressure losses (Fig 5).

Minimum clearances

Observe the minimum clearances to allow access for maintenance and
repair work and facilitate optimum air distribution.

300

300

300

300

300

E

C

B

A

D

Air intake

Air outlet

All values in mm

Minimum clearances

Ensure a continuous and unob-
structed air flow from outside,
preferably using sufficiently
large air intakes placed opposite
each other (Fig 5).

Comply with any regulations
and conditions affecting the
statics of the building. If neces-
sary, fit acoustic installation.

Oil return measures

If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed
for every 2.5 metres of height
difference.

Oil return measures

SV 261 AT

SV 351 AT

SV 521 AT

SV 681 AT

A

100 mm

150 mm

B

700 mm

900 mm

C

400 mm

D

100 mm

150 mm

E

200 mm

400 mm

600 mm

Outdoor

component

Oil pump bend

in suction pipe

to outdoor

component one

every 2.5 metres of

rising pipe

Radius:

50 mm

max. 15 m

Indoor unit