beautypg.com

Installation instructions for qualified personnel – REMKO SV 261 User Manual

Page 17

background image

Installation instructions for qualified personnel

Transport the unit in its original
packaging as close as possible
to the installation location.This
avoids transportation damage.

Check that the packaged
contents are complete and
inspect the unit for any visible
signs of transportation damage.
Immediately notify any
deficiencies to the contractual
partner and forwarding agent.

Lift the unit by its corners
and not the refrigerant or
condensation connections.

Insulate the refrigerant pipes
(injection and suction pipe),
valves and connections to make
them tight against vapour
diffusion.If necessary also
insulate the condensation pipe.

Select an installation location
which allows air to freely
flow through the inlet and
outlet.(see section "Minimum
clearances").

Do not install the unit
adjacent to any hotspots.Unit
performance will be impaired if
installed next to hotspots.

Only open the stop valves
for the refrigerant pipes after
installation has been fully
completed.

Use caps or adhesive tape to
seal off the open refrigerant
pipes and prevent the ingress of
humidity.
Never kink or push in the
refrigerant.

Avoid unnecessary bending.
This minimises the pressure
loss in the refrigerant pipes and
ensures that the compressor
oil can flow back without
obstruction.

Special measures concerning
the oil return pipe must be
taken if the outdoor component
is mounted above the indoor
unit.
(See section "Oil return
measures").

Add refrigerant if the basic
length of the refrigerant pipe
exceeds 5 metres.
The amount of additional
refrigerant is given in the
chapter "Adding refrigerant".

Only use the union nuts
supplied with the refrigerant
pipes. These should only
be removed shortly before
connecting the refrigerant
pipes.

Establish all electrical
connections in accordance with
the relevant DIN- and VDE
standards.

Connect the electrical cables
properly to the terminals.
Otherwise there is a risk of fire.

Service openings should be
provided in the suspended
ceiling to allow maintenance
access to the control box.

Any ventilation ducts or pipes
and connection fittings, which
are used to connect a second
room or supply fresh air, should
be insulated with

diffusion-tight

material.

Wall breakthroughs

The wall breakthrough must
have a diameter of min. 70 mm
and a fall of 10 mm from inside
to outside for each indoor unit.

We recommend that the
inside of the hole is padded or
lined, e.g. using a PVC tube,
to prevent the pipes being
damaged.

After installation has been
completed, use a suitable
sealing compound to close
off the wall breakthrough
(responsibility of customer).
Do not use cement- or lime-
based materials!

Important points prior to
installation

Control cable

Condensation pipe

Injection pipe

Suction pipe

PVC tube

Pipes and cables in wall breakthrough

17