Installation

Installing the unit

The indoor unit is mounted face

down on four threaded rods. Take

into account the ceiling grid and

any other installations.

1. Use the dimensions of the

ceiling cassette (Fig 8) to

mark the fixing points for the

threaded rods on structural

parts approved to support the

static load above the suspended

ceiling.

2. Fit any connection nozzles

before installing the unit

if connections to a second

room or a fresh air intake are

required.

Installation should only be
performed by authorised
specialists.

NOTE

8 Mounting the unit

280

615

Dimensions in mm

SV 261-681

Distance A

35 mm

Distance B

25 mm

Mounting the unit

615 mm x 280 mm

9 Hooking in the unit

See section Connections to

a second room or a fresh air

intake.

3. Fit the indoor unit onto the

threaded rods and use the

lower nuts to level the unit

(Fig 9)

.

This ensures that the

condensation drains into the

collection tray.

4. Make sure that clearance A,

(Fig 10)

as specified in the table

below, is provided between the

underside of the suspended

unit and the underside of the

fastening surface.

5. Connect the refrigerant

pipes, electrical cables and

condensation pipe to the indoor

unit as described below.

6. Check that the unit is level.

The units are factory filled with

dry nitrogen to check for leaks.

The pressurised nitrogen is

released when loosening the

union nuts.

CAUTION

7. The final task is to tighten the

counternuts and attach the

cover.

10 Fastening the unit

Structural component

Structural component

B

A

All dimensions in mm

Connecting the refrigerant
pipes

The connections to the refrigerant
pipes are made at the rear of the
unit (responsibility of customer).

It may be necessary to fit a reducer
or flared adapter to the indoor
unit. These fittings are included
as standard. Once installed, the
connections should be made tight
against vapour diffusion.

The procedures for installing the

refrigerant circuit and mounting

the indoor unit and outdoor

component are described below.

1. The required pipe diameters are

given in the table "Technical

data"

REMKO SV