Keys
Cooling mode
Automatic mode
MODE Key
Use the MODE key to select between individual operating modes.
5 modes are available:
Using the key, the target temperature can be adjusted up or down by
1°C. The temperature range lies between 17°C and 30°C
1. Automatic
cooling or heating mode
2. Cooling
mainly a summer operating mode
3. Dehumidification summer or winter operating mode
4. Heating
mainly a winter operating mode
5. Circulation
air circulation only
MODE
MODE
MODE
Automatic
Cooling
Dehumidification
Heating
Circulation
▼
▲
▼
▲
In automatic mode, the controller autonomously selects between heating,
circulation or cooling mode based on the room temperature Tr and
the selected target value Ts. The target value can be adjusted between
17°C and 30°C by means of the
▲/▼ keys. Fan speed is selected
automatically.
AUTOMATIC MODE
AUTOMATIC
MODE
Operating sequence:
If Tr is 1K less than Ts, then operating mode "Heating" is selected.
If Tr is 2K greater than Ts, then operating mode "Cooling" is selected.
If Tr is between Ts -1K and Ts +2K, then operating mode "Circulation" is selected.
If the compressor is shut down within an operating mode and then not required for more than 15 mins, if the
room temperature deviates, the corresponding mode heating, cooling or circulation will be selected again.