beautypg.com

Technical data – REMKO RXT xxx DC User Manual

Page 51

background image

Technical data

Series

RXT 351DC

RXT 521DC

RXT 681DC

RXT 1051DC

RXT 1401DC

Operating mode

Inverter wall-mounted room air conditioner combination for cooling and heating

Nominal cooling output

1)

kW

3,51 (1,41-4,02)

5,27 (1,63-5,65)

7,03 (1,63-7,92) 10,55 (3,01-13,22) 14,01 (3,41-15,62)

Nominal heating output

2)

kW

4,02 (1,42-4,75)

5,86 (1,45-6,15)

7,76 (1,75-8,61) 11,72 (3,75-14,02) 15,47 (4,23-16,5)

Energy efficiency rating, cooling

1)

A

A

A

A

A

Energy efficiency rating EER

1)

3,54

3,34

3,22

3,25

3,23

Energy efficiency rating, heating

2)

A

A

B

A

A

Coefficient of performance COP

2)

3,75

3,86

3,42

3,64

3,62

Power consumption, yearly,

(500h) C / H

495 / 535

790 / 760

1090 / 1060

1625 / 1515

2165/2135

Usage area

(room volume), approx.

110

160

230

320

470

Refrigerant

R 410A

4)

Power supply

V/Hz

230 / 1~ / 50

400 / 3~ / 50

Rated electr. power

consumption, cooling

1)

kW

0,99 (0,32-1,27)

1,58 (0,44-2,32)

2,18 (0,84-2,35)

3,25 (2,31-5,02)

4,33 (2,51-5,95)

Rated electr. power

consumption, heating

2)

kW

1,07 (0,36-1,38)

1,52 (0,36-2,44)

2,12 (0,72-2,72)

3,03 (1,03-3,91)

4,27 (1,45-5,51)

Max. rated electr. power

consumption

kW

2,55

2,40

3,25

5,00

5,50

Rated electr. current

consumption, cooling

1)

A

4,67 (1,68-5,90)

7,09 (1,95-10,5) 10,30 (3,65-11,52) 4,72 (3,30-7,53)

6,27 (3,60-8,53)

Rated electr. power

consumption, heating

2)

A

5,05 (1,89-6,41)

6,81 (1,65-11,6) 10,05 (3,22-12,81) 4,47 (1,49-5,98)

6,19 (2,08-8,48)

Electr. starting current, max.

A

12

14

15,5

7,5

7,8

Refrigerant connection,

injection line

Inches

(mm)

1/4 (6,35)

1/4 (6,35)

3/8 (9,52)

3/8 (9,52)

3/8 (9,52)

Refrigerant connection,

suction line

Inches

(mm)

1/2 (12,70)

1/2 (12,70)

5/8 (15,90)

5/8 (15,90)

5/8 (15,90)

Max. operating pressure

kPa

4200 / 2500

Data specific to

indoor unit

RXT 351DC IT RXT 521DC IT RXT 681DC IT RXT 1051 DC IT RXT 1401DC IT

Setting range for room temperature

°C

+17 to +30

Operating range

°C

+17 to +32

Air flow volume per speed setting

m³/h

460/520/580

500/600/800 960/1080/1150 1000/1200/1400

1600/1800/2000

Sound pressure level per speed setting

3)

dB(A)

33/37/40

38/41/43

40/43/46

40/43/45

44/46/47

Protection class

IP

X0

Condensation connection

mm

25

Dimensions - Height

mm

660

660

660

660

680

Width

mm

990

990

990

1280

1670

Depth

mm

206

206

206

206

245

Weight

kg

27,0

29,0

29,0

37

52

Data specific to

outdoor

component

RXT 351DC AT RXT 521DC AT RXT 681DC AT RXT 1051DC AT RXT 1401DC AT

Operating range, cooling

°C

+5 to +43

Operating range, heating

°C

-15 to +34

Air flow rate, max.

m³/h

1600/2500

2300/2570

3000 /3250

4800 /5000 5800 /6000

Protection class

IP

24

Sound pressure level, max.

3)

dB(A)

48

51

53

55

59

Refrigerant, basic quantity

kg

1,40

1,60

2,30

2,9

3,6

Refrigerant, additional quantity > 5 m

g/m

30

30

30

30

30

Refrigerant pipe, max. length

m

15

25

25

30

50

Refrigerant pipe, max. height

m

10

10

10

15

20

Flow regulator

Capillary tube

Electronic

Electronic

Electronic

Electronic

Dimensions - Height

mm

590

695

860

990

1245

Width

mm

760

845

895

960

940

Depth

mm

280

325

335

360

360

Weight

kg

39,0

59,0

73,0

87,0

99,0

Serial number

1034...

1035...

1036...

1037...

1038...

EDP no.

1619430

1619440

1619450

1619460

1619470

1) Air intake temperature TK 27°C / FK 19°C, outdoor temperature TK 35 °C, FK 24 °C, max. air flow volume, 5m pipe length
2) Air intake temperature TK 20°C, outdoor temperature TK 7°C, FK 6°C, max. air flow volume, 5m pipe length
3) Gap 1 m free space 4) Contains greenhouse gas according to Kyoto Protocol

51