RXT 521-1401DC indoor unit fault analysis

10. Operation light flashes at 5 Hz and Defrost light is on: Hot gas temperature too high

Is the temperature of
the Klixon over 115°C?

Yes

Fix the leak and top up

No

No

Establish a proper
connection

Yes

Yes

Is there a
refrigerant leak?

Is the connection
between the Klixon and
circuit board OK?

Is the resistance value
for the Klixon correct
(Table 2, P95)?

No

Replace Klixon

Yes

Replace outdoor
component main board

Is the resistance of the
vaporiser sensor OK
(Table 1, P92-94)?

Replace temperature
sensor

No

1. Operation light flashes at 5 Hz: fault on the
vaporiser sensor or room sensor

Yes

Is the resistance of the
room sensor OK
(Table 1, P92-94)?

Yes

Replace indoor unit
main board

No

Replace temperature
sensor