Installation instructions for qualified personnel

Important notes prior to
installation

Transport the unit in its original
packaging as close as possible
to the installation location.
You avoid transport damages
by doing so.

Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report any
damage immediately to your
contractual partner and the
shipping company.

Lift the unit at the corners
and not by the refrigerant or
condensation connections.

The refrigerant pipes
(injection and suction line),
valves and connections must
be insulated against vapour
diffusion. If necessary, also
insulate the condensation pipe.

Select an installation location
which allows air to freely
flow through the intake and
outlet (see section "Minimum
clearances").

Do not install the unit in the
immediate vicinity of devices
which generate intensive
thermal radiation. Installation
near sources of thermal
radiation reduces the output of
the unit.

Only open the shut-off valves
of the refrigerant pipes after
installation is complete.

Seal off open refrigerant pipes
with suitable caps or adhesive
strips to avoid infiltration of
moisture and never kink or
compress the refrigerant pipes.

Avoid unnecessary bends.
This minimises the pressure
loss in the refrigerant pipes and
ensures that the compressor
oil can flow back without
obstruction.

Make special preparations
regarding the oil return if
the outdoor component is
located above the indoor unit
(see section "Oil return flow
measures").

If the basic length of the
refrigerant pipe exceeds
5 metres, add refrigerant.
The quantity of additional
refrigerant is provided in the
chapter "Adding refrigerant".

Only use the union nuts for the
refrigerant pipes included in the
delivery, and remove them only
shortly before connecting the
refrigerant pipes.

Make all electrical connections
in accordance with applicable
DIN and VDE standards.

Always fasten electric cables
properly to the electrical
terminals. Otherwise a fire
could result.