beautypg.com

REMKO RXT xxx DC User Manual

Page 43

background image

9. Fault code P4: hot gas temperature too high

Is the hot gas
temperature over 115°C?

Yes

Is the connection
between the sensor
and circuit board OK?

No

Is the resistance value
for the sensor correct
(Table 2, P95)?

Replace
hot gas sensor

Yes

No

Replace outdoor
component main board

Fix the leak and top up

Yes

Is there a
refrigerant leak?

No

Establish a proper
connection

No

10. Fault code P5: condenser outlet sensor triggered

Is the condenser outlet
temp. greater than
65°C?

Yes

Clean condenser
register

Is the outdoor
temperature too high?

Yes

Switch off unit

No

Replace
sensor

Check the resistance
of the sensor. (Table 1,
P92-94)
Is the resistance OK?

Yes

Replace outdoor
component main board

No

Replace outdoor
component main board

No

Is the condenser
register dirty?

Are the refrigerant
pipes blocked or bent?

Siphon off refrigerant,
replace pipe / remove
blocked, perform
pressure test, drawn
vacuum and refill

Yes

No

No

Yes

43