9. Fault code P4: hot gas temperature too high
Is the hot gas
temperature over 115°C?
Yes
Is the connection
between the sensor
and circuit board OK?
No
Is the resistance value
for the sensor correct
(Table 2, P95)?
Replace
hot gas sensor
Yes
No
Replace outdoor
component main board
Fix the leak and top up
Yes
Is there a
refrigerant leak?
No
Establish a proper
connection
No
10. Fault code P5: condenser outlet sensor triggered
Is the condenser outlet
temp. greater than
65°C?
Yes
Clean condenser
register
Is the outdoor
temperature too high?
Yes
Switch off unit
No
Replace
sensor
Check the resistance
of the sensor. (Table 1,
P92-94)
Is the resistance OK?
Yes
Replace outdoor
component main board
No
Replace outdoor
component main board
No
Is the condenser
register dirty?
Are the refrigerant
pipes blocked or bent?
Siphon off refrigerant,
replace pipe / remove
blocked, perform
pressure test, drawn
vacuum and refill
Yes
No
No
Yes
43
- RKL 491 DC S-LINE (28 pages)
- RKL 360 S-LINE (28 pages)
- MKT 291 S-LINE (28 pages)
- BL 352 DC (56 pages)
- ML 523 DC (64 pages)
- MXD 522 (48 pages)
- MXW 522 (44 pages)
- PWL 303 HK (24 pages)
- RVT 683 DC (72 pages)
- WLT 85 (24 pages)
- RVS 150 H (44 pages)
- KWL Series (48 pages)
- MKT 240 (12 pages)
- MKT 250 (12 pages)
- MKT 260 (16 pages)
- RKL 350 (16 pages)
- MKT 290 (20 pages)
- RKL 480 (16 pages)
- RKL 240 (16 pages)
- RKL 490 DC (20 pages)
- ATY 351 (28 pages)
- ATY 350 (32 pages)
- ATY 351 DC (36 pages)
- MD 351 (32 pages)
- ML 280 (24 pages)
- BL 351 (32 pages)
- ML 522 DC (32 pages)
- MVT 1050 DC (28 pages)
- MXD 520 v.3 (28 pages)
- MXD 520 v.1 (28 pages)
- RKS 448 H (20 pages)
- RKS 524 H (16 pages)
- RKS 371 H (28 pages)
- RKV 24 W (20 pages)
- RKV 24 T (20 pages)
- RKV 24 C (24 pages)
- RKW INOX (28 pages)
- RVD 521 DC (32 pages)
- RM Series (36 pages)
- RVD xxx DC (52 pages)
- RWH 680 (20 pages)
- RVT 521 DC (32 pages)
- RXS xxx H (20 pages)
- RXD Series (28 pages)
- RXW 480 (20 pages)