Installation inside buildings

Ensure that heat can dissipate
adequately when placing the
outdoor component in cellars,
lofts, adjoining rooms or halls
(Fig. 4)

.

Install an additional fan with
a rated flow comparative to
that of the outdoor component
being installed in the room.
This is used in conjunction with
ventilation ducts to compensate
any pressure losses (Fig. 4).

Ensure a continuous and
unobstructed air flow from
outside, preferably using
sufficiently large air intakes placed
opposite each other (Fig. 4).

Comply with any regulations
and conditions affecting the
structure of the building.
If necessary, fit acoustic
insulation.

Minimum clearances

Observe the minimum clearances
to allow access for maintenance
and repair work and facilitate
optimum air distribution.

RXT 351DC

AT

RVT 521-

1401DC AT

A

300 mm

B

2000 mm

C

600 mm

D

200 mm

E

400 mm

Warm air

Cold

fresh air

Lightwell

shaft

Outdoor component

Warm air

Lightwell

shaft

Additional

fan

4 Installation inside buildings

Minimum clearances

All dimensions are given in mm

E

C

B

A

D

Air intake

Air outlet

Oil return measures

If the outdoor component is
installed at a higher level than the
indoor unit, suitable
oil return measures must be taken.
This is normally accomplished by
creating
a bend in the oil line, installed at
every 2.5 metres of rise.

Oil return measures

Outdoor

component

Oil pump bend

in suction pipe to

outdoor component

1 x every 5 metres

of rise in the line

Radius:

Min. 50 mm

Max. see P51

Indoor unit

Minimum clearances

800

50

50

Wall installation

Ceiling installation

700