Fault indication by flashing code

Sensor resistance

Opera-

tion

LED

Timer

LED

Defrost

fan

LED

Alarm

LED

OC

display

Cause

Required action

Flashes

rapidly

Flashes

rapidly

E0

EEPROM error

Check that EEPROM is firmly
in place

*Flashes

slowly

E2

Communication error between OC &
IU PCBs

Check electrical connection
leads

For RXT 1051 DC and up

E3

Communication error between OC
main board & OC inverter board

Check wiring

** Flashes

slowly

E4

Outdoor temp. sensor on OC tripped

Check resistance and
temperature on sensor

E5

Compressor overvoltage

Check compressor voltage

P0

Compressor excess temperature

Allow compressor to cool

P1

High pressure switch has triggered

Check refrigerant pressure

P2

Low pressure switch has triggered

Check refrigerant pressure

P3

Compressor power consumption too high

Check compressor power
consumption

P4

Hot gas temperature over 105°C

Clean condenser, check
refrigerant circuit

P5

Condenser temperature over 65°C

Clean condenser, check
refrigerant circuit

P6

Voltage protection, OC main board

Check voltage

Flashes

rapidly

* Flashes

rapidly

Air circulation / condenser sensor
tripped

Check resistance

Flashes

rapidly

Communication error between OC & IU

Check electrical connection
leads

Flashes

rapidly

Operating mode fault

Switch system off

Flashes

slowly

Flashes

slowly

Flashes

slowly

Flashes

slowly

Condenser / outdoor temp. sensor
faulty or not correctly connected

Read off fault code on OC
Check sensors

IT vaporiser sensor, IT circulation sensor

Temperature °C

Resistance

0

35.20 k

Ω

5

26.88 k

Ω

10

20.72 k

Ω

15

16.12 k

Ω

20

12.64 k

Ω

25

10.00 k

Ω

30

7.97 k

Ω

35

6.40 k

Ω

* RXT 521 DC ** RXT 681 DC