7. Fault code P2: low pressure fault

Is the connecting cable
from the lower pressure
switch to the main
board OK?

Correct
connection

No

Yes

Low pressure switch
may be defective

Bypass the low pressure
switch on the circuit
board. Does the unit
work now?

Replace the high
pressure switch

Yes

Switch off unit

No

Yes

Is the outdoor
temperature too low?

Check refrigerant
pipes

The refrigerant pipes
may be leaking

No

Check the refrigerant
pipes with leak
detection spray or an
electronic leak detector

Yes

Check the refrigerant
pressure with a
manometer. Is the
refrigerant pressure less
than 1.4 bar?

Refrigerant pipe may
be blocked

No

Siphon off refrigerant,
replace pipe / remove
blocked, perform
pressure test, drawn
vacuum and refill

No

Replace outdoor com-
ponent main board

41