beautypg.com

Remko rxt...dc – REMKO RXT xxx DC User Manual

Page 40

background image

6. Fault code P1: high pressure fault

Is the connecting cable
from the high pressure
switch to the main
board OK?

Correct
connection

No

Yes

High pressure switch
may be defective

Bypass the high
pressure switch on the
circuit board. Does the
unit work now?

Replace the high
pressure switch

Yes

Switch off unit

No

Yes

Is the outdoor
temperature too high?

Check refrigerant
pipes

Is the function of the
fan on the outdoor
component OK?

No

No

Ensure fan functions
properly

Clean the register of the
outdoor component

Yes

Is the register of the
outdoor component dirty?

Siphon off refrigerant,
replace pipe / remove
blocked, perform
pressure test, drawn
vacuum and refill

Yes

Are the refrigerant
pipes blocked or bent?

No

Replace outdoor
component main board

Yes

REMKO RXT...DC

40