6. Fault code P1: high pressure fault
Is the connecting cable
from the high pressure
switch to the main
board OK?
Correct
connection
No
Yes
High pressure switch
may be defective
Bypass the high
pressure switch on the
circuit board. Does the
unit work now?
Replace the high
pressure switch
Yes
Switch off unit
No
Yes
Is the outdoor
temperature too high?
Check refrigerant
pipes
Is the function of the
fan on the outdoor
component OK?
No
No
Ensure fan functions
properly
Clean the register of the
outdoor component
Yes
Is the register of the
outdoor component dirty?
Siphon off refrigerant,
replace pipe / remove
blocked, perform
pressure test, drawn
vacuum and refill
Yes
Are the refrigerant
pipes blocked or bent?
No
Replace outdoor
component main board
Yes
REMKO RXT...DC
40
See also other documents in the category REMKO Conditioners:
- RKL 491 DC S-LINE (28 pages)
- RKL 360 S-LINE (28 pages)
- MKT 291 S-LINE (28 pages)
- BL 352 DC (56 pages)
- ML 523 DC (64 pages)
- MXD 522 (48 pages)
- MXW 522 (44 pages)
- PWL 303 HK (24 pages)
- RVT 683 DC (72 pages)
- WLT 85 (24 pages)
- RVS 150 H (44 pages)
- KWL Series (48 pages)
- MKT 240 (12 pages)
- MKT 250 (12 pages)
- MKT 260 (16 pages)
- RKL 350 (16 pages)
- MKT 290 (20 pages)
- RKL 480 (16 pages)
- RKL 240 (16 pages)
- RKL 490 DC (20 pages)
- ATY 351 (28 pages)
- ATY 350 (32 pages)
- ATY 351 DC (36 pages)
- MD 351 (32 pages)
- ML 280 (24 pages)
- BL 351 (32 pages)
- ML 522 DC (32 pages)
- MVT 1050 DC (28 pages)
- MXD 520 v.3 (28 pages)
- MXD 520 v.1 (28 pages)
- RKS 448 H (20 pages)
- RKS 524 H (16 pages)
- RKS 371 H (28 pages)
- RKV 24 W (20 pages)
- RKV 24 T (20 pages)
- RKV 24 C (24 pages)
- RKW INOX (28 pages)
- RVD 521 DC (32 pages)
- RM Series (36 pages)
- RVD xxx DC (52 pages)
- RWH 680 (20 pages)
- RVT 521 DC (32 pages)
- RXS xxx H (20 pages)
- RXD Series (28 pages)
- RXW 480 (20 pages)