8. Fault code P3: compressor overcurrent protection
has tripped
Is the input current
greater than 20A?
Check refrigerant pipes
No
Yes
Is the outdoor
temperature too high?
Switch off unit
Yes
Yes
Is the function of the
fan on the outdoor
component OK?
No
Ensure fan functions
properly
Is the register of the
outdoor component
dirty?
Are the refrigerant
pipes blocked or bent?
Yes
Siphon off refrigerant,
replace pipe / remove
blocked, perform
pressure test, drawn
vacuum and refill
Clean the register of the
outdoor component
No
Replace outdoor
component main board
No
Yes
No
REMKO RXT...DC
42
See also other documents in the category REMKO Conditioners:
- RKL 491 DC S-LINE (28 pages)
- RKL 360 S-LINE (28 pages)
- MKT 291 S-LINE (28 pages)
- BL 352 DC (56 pages)
- ML 523 DC (64 pages)
- MXD 522 (48 pages)
- MXW 522 (44 pages)
- PWL 303 HK (24 pages)
- RVT 683 DC (72 pages)
- WLT 85 (24 pages)
- RVS 150 H (44 pages)
- KWL Series (48 pages)
- MKT 240 (12 pages)
- MKT 250 (12 pages)
- MKT 260 (16 pages)
- RKL 350 (16 pages)
- MKT 290 (20 pages)
- RKL 480 (16 pages)
- RKL 240 (16 pages)
- RKL 490 DC (20 pages)
- ATY 351 (28 pages)
- ATY 350 (32 pages)
- ATY 351 DC (36 pages)
- MD 351 (32 pages)
- ML 280 (24 pages)
- BL 351 (32 pages)
- ML 522 DC (32 pages)
- MVT 1050 DC (28 pages)
- MXD 520 v.3 (28 pages)
- MXD 520 v.1 (28 pages)
- RKS 448 H (20 pages)
- RKS 524 H (16 pages)
- RKS 371 H (28 pages)
- RKV 24 W (20 pages)
- RKV 24 T (20 pages)
- RKV 24 C (24 pages)
- RKW INOX (28 pages)
- RVD 521 DC (32 pages)
- RM Series (36 pages)
- RVD xxx DC (52 pages)
- RWH 680 (20 pages)
- RVT 521 DC (32 pages)
- RXS xxx H (20 pages)
- RXD Series (28 pages)
- RXW 480 (20 pages)