beautypg.com

2 technical data, 1 technical data, Technical data 2.1 technical data – REMKO MXD 202 User Manual

Page 7: Technical data

background image

2

Technical data

2.1

Technical data

Series

MXD 202

MXD 262

MXD 352

MXD 522

Operating mode

Ceiling cassette for inverter multi-split designed outdoor

units for cooling and heating

Nominal cooling output

1)

kW

2,05

2,64

3,51

5,27

Nominal heating output

2)

kW

2,34

3,22

3,81

6,00

Operating range (room volume),

approx.

m

3

60

80

110

160

Room-temperature adjustment range

°C

+17 to +30

Operating range

°C

+17 to +32

Refrigerant

R 410A

4)

Operating pressure max. / per cooling

circuit

kPa

4200 / 1500

Air flow volume per speed setting

m³/h

380/445/580 380/445/580 500/570/720 635/690/800

Sound press. level per speed setting

3)

dB (A)

40/44/48

40/44/48

40/43/48

40/43/46

Sound power (Turbo mode)

dB (A)

52

53

54

54

Power supply

V/Hz

230 / 1~ / 50

Protection class

IP

X 0

Nom. electrical power consumption,
cooling

1)

W

15

15

20

102

Nom. electrical power consumption,
heating

2)

W

15

15

20

102

Nom. electrical current consumption,
cooling

1)

A

0,06

0,06

0,08

0,44

Nom. electrical power consumption,
heating

2)

A

0,06

0,06

0,08

0,44

Refrigerant connection - injection line

Inch

(mm)

1/4 (6,35)

1/4 (6,35)

1/4 (6,35)

1/4 (6,35)

Coolant connection - suction line

Inch

(mm)

3/8 (9,52)

3/8 (9,52)

3/8 (9,52)

1/2 (12,70)

Condensate drain

mm

25

25

25

25

Condensate pump, max. pumping

capacity

mm

WS

500

7