beautypg.com

Remko mxd – REMKO MXD 202 User Manual

Page 24

background image

Connecting the refrigerant lines

Bby customer on-site connecting the refrigerant lines are at a corner of the unit within the false ceiling. It may

be necessary to fit a reducing or extending adapter to the indoor units. These fittings are included with the

indoor unit as an accessory kit. Once installed, the connections should be sealed to prevent vapour diffusion.

Performence

Indoor unit

Refrig-

erant pipe

Indoor unit MXD 202-522

Indoor unit

Con-

necting

Reducing / extending

Refrig-

erant pipe

Reducing / extending

Con-

necting

EL

SL

SL

EL

SL

SL

EL

SL

2,0 kW

1/4" 3/8"

-

1/4" 3/8"

-

1/4" 3/8"

2,6 kW

1/4" 3/8"

-

1/4" 3/8"

-

1/4" 3/8"

3,5 kW

1/4" 3/8"

-

1/4" 3/8"

-

1/4" 3/8"

5,2 kW

1/4" 3/8"

Erw. 3/8" AT -> 1/2" IT

1/4" 1/2"

-

1/4" 1/2"

Note: SL = Suction pipe (large pipe), EL = injection pipe (small pipe)

Adjacent room and fresh air connection

The indoor unit is designed to cool an adjacent

second room and, independently of this, to suction

in fresh air.

2

1

2

Fig. 29: Adjacent room and fresh air connection

1: Fresh air connection

2: Adjacent room connection

NOTICE!

Only one adjacent room connection and one

fresh air connection may be used!

NOTICE!

The unit is factory filled with dry nitrogen for

leak testing purposes. The pressurised

nitrogen is released when the union nuts are

undone.

Installation instructions

To install the fresh air connection and the connec-

tion for the adjacent room, proceed as follows:

1.

Remember that directly behind the insulation

to be removed are the plate fins of the hea-

texchanger and that these may by no means

be damaged (Fig. 30).

2.

Carefully remove the insulation behind the

opening. (Fig. 31).

3.

Break through the corresponding openings

(Fig. 32).

4.

Keep the vent pipe as short as possible and

lay it with as few bends as necessary.

5.

Keep in mind that the flanged collar, screws,

flexible/folded spiral-seam pipes and insula-

tion materials must be provided by the cus-

tomer. These parts can all be purchased

from your dealer. (Fig. 33).

REMKO MXD

24

This manual is related to the following products: