Condensate connection

and safe drainage

n

The condensate tray should have an incline of

min. 2%. This is the responsibility of the cus-

tomer. If necessary, fit vapour-diffusion-proof

insulation.

n

IIf the level of the condensation pipe on the unit

is above that of the outlet, route the pipe verti-

cally upwards and then with a fall to the drain

n

Guide the unit’s condensation pipe into the

drain pipe. If the condensation is being guided

to a drainage pipe, please install a siphon-like

hose guideway which acts as an odour seal.

The diameter of the condens connecting piece

is 25 mm.

n

When operating the unit at outside tempera-

tures below 4 °C, ensure the condensate

drainage is laid to protect it against frost. The

lower part of the housing and condensate tray

is also to be kept frost free in order to ensure

permanent draining of the condensate. If nec-

essary, fit a pipe heater.

n

Following installation, check that the conden-

sate run off is unobstructed and ensure that the

line is durably leak tight.

Condensate draining

If the temperature falls below the dew point, con-

densation will form on the cooling fins during

cooling mode. A collection tray together with a con-

densation pump and float switch are fitted as

standard below the cooling fins. Should the float

switch trip a protective shutdown due to inade-

quate removal of the condensation, the pump will

switch on immediately and run on for approx. three

minutes.

Ensured discharge in the event of leakage

NOTICE!

Local regulations or environmental laws, for

example the German Water Resource Law

(WHG), can require suitable precautions to

protect against uncontrolled draining in case of

leakage to provide for safe disposal of

escaping refrigerator oil or hazardous media.

NOTICE!

The maximum capacity of the condensate

pump is 500 mm WS. External influences, such

as air-side back pressure, contamination, or

wear may cause a reduction in performance.

To ensure safe operation function, we recom-

mend a maximum conveyor height of 450 mm

should not be exceeded!

A

C

B

D

Fig. 37: Condensate connection - wrong!

A: Faraway riser

B: To large/small condensate pipe

C: No slope

D: No free outlet

16-20 mm

min. 2%

max.

500 mmWS

Fig. 38: Condensate connection - right!

27