REMKO MXD 202 User Manual
Page 17
![background image](https://www.manualsdir.com/files/801967/content/doc017.png)
"Automatic" mode
In automatic mode, the controller autonomously
selects between heating, circulation or cooling
mode based on the room temperature Tr and the
selected target value Ts. The target value can be
adjusted between 17°C and 30°C by means of the
" " and " ". The fan speed is selected automati-
cally.
Fig. 12: "Automatic" mode
Funktion:
Tr
selected.
Tr>Ts=2 °C, then operating mode "Cooling" is
selected.
Tr<-1 °C...Ts...+2 °C, then operating mode "Circu-
lation" is selected.
If after the compressor is shut down and not
required for more than 15 mins. within an operating
mode, then, in the event that the room temperature
deviates, the corresponding mode heating,
cooling or circulation will be selected again.
The heating mode has priority!
Turns on the indoor unit to the heating mode,
switch off the other indoor units from which are
in cooling mode, the cooling. During heating
operation can not be cooled.
„Dehumidification“ mode
It is recommended that the target temperature be
set to 24°C in dehumidifying mode. Due to the low
temperature of the refrigerant, the dew point of the
air at the condenser is undercut. The excess mois-
ture in the air is condensed by the vaporiser, the
room is dehumidified.
Fig. 13: "Dehumidification“ mode
„Cooling“ mode
In cooling mode, the air in the room is cooled down
to the adjusted nominal temperature. The desired
room temperature is set with the " " and " " keys
in 1 °C increments. If the room temperature is 0.5
°C above the selected nominal temperature, then
the interior unit starts to cool down the air in the
room. If the temperature falls to approx. 1 °C below
the set room temperature, the controller will switch
off the cooling function. To protect the compressor,
the controller only turns cooling on again after a
waiting period of 3 minutes.
Fig. 14: „Cooling“ mode
17